Description
The functional module “WB-VDC” is used wherever power voltages from 200VDC are measured and monitored. In addition, based on the data collected, control decisions can be passed on to third-party systems.
Application examples include:
- Feed-in points of substations in railway infrastructure
- Return conductor points from substations in railway infrastructure
- in the generation of energy and its storage
- truck charging stations
- BOAT charging station
- train charging stations
- power battery in a BOAT
General data
|
Supply voltage
|
24VDC /100mA
|
|
Power consumption
|
5W – 15W
|
|
humidity
|
0 …100%, non-condensing
|
|
Outside temperature range
|
-20 … 50 °C
|
|
housing / design
|
T2 (1 TE = 18 mm) (W x H x D) 36mm x 99mm x 105mm
If option WB-MC T3 (W x H x D) 68mm x 99mm x 105mm
If option measurement display T4 (W x H x D) 90mm x 99mm x 105mm
|
|
Modular housing
|
|
Protection class IP 20
|
|
Mounted on 35 mm DIN rail according to EN 60715
|
|
Mains connection and inputs and outputs:
|
– screw terminals,
– Stripping length 9…10 mm
Note: For connecting potential-free contacts to
the actuator inputs are twisted pair wires
wires to use.
The following conductor cross-sections are permitted:
– solid 0.5 … 2.5 mm2
– finely stranded, with pin cable lug, gas-tight crimped 0.5… 2.5 mm²
– Finely stranded, with ferrule 0.5 … 1.5 mm2
– Finely stranded, untreated 1.0 and 1.5 mm²
|
|
weight
|
approx. 250g
|
Parameterization
For security reasons and by popular request, there was no on-site configuration option.
The threshold values can be set at the factory.
If you need several different threshold values in your systems, you can do this using the CM1010 / VLD1010 service case. Different parameter sets and software updates can be stored on the service case and imported using an adapter.
It is also possible to transfer the parameters via a SCADA system (the system must be configured using a WB-MC or WB-HS must be connected).
Technical specifications
Standard WB VDC
Analogue input channels (measuring channels)
The nominal voltages are based on the typical power supply of DC railways.
|
|
|
|
|
|
max. Measuring range
|
+/-345V
|
+/-860V
|
+/-1725V
|
+/-3450V
|
|
max. Rated voltage VDC
|
300
|
750
|
1500
|
3000
|
|
Voltage strength VDC
|
1000 / 10sek
|
2000 / 10sec
|
3000 / 10sek
|
6000 / 10sek
|
|
|
|
|
|
|
Measurement accuracy
|
see measurement channel variants
|
We provide two variants of measurement channels:
|
Product type
|
withe line
|
silver line
|
|
Measuring channels
|
2
|
|
Sampling rate
|
up to 15kHz
|
up to 25kHz
|
|
Resolution
|
up to 8 bits
|
up to 16 bit
|
|
Measurement accuracy
|
5% of max. value
|
0.5% of max. value
|
Output channels digital
|
number
|
2
|
|
Technology
|
Relay with 2 separate changeover contacts (NC/ NO)
|
|
switching voltage
|
max. 250V
|
|
switching current
|
max. 8A
|
|
switching capacity
|
max. 2000VA / 60W
|
|
Dielectric strength coil – contact
|
max. 4kVAC
|
|
Switching cycles at Imax
|
> 1,000,000
|
|
electrical strength contact-contact
|
max. 2000VAC
|
Show
Possible variants depending on the range of functions or options
|
LED1
|
green
|
Run
|
operability permanently ON
|
|
LED2
|
blue
|
Enable
|
Approval granted by higher authority
|
|
LED3
|
green
|
ON/ OFF
|
Sonicated On / OFF
|
|
LED4
|
red
|
Error
|
Functional malfunction of the system or sensors or equipment
|
Operation
No controls are provided in the standard system.
Function
The following measurement functions can be carried out, evaluated and displayed using the digital outputs or, if available, transmitted via a protocol
-
Detects high and low voltage
-
DC voltage measurement
-
AC voltage measurement
-
Measurement of mixed voltage
-
Storage of maximum DC voltage value (since last reset)
-
Save max voltage value AC (since last reset)
Voltage up to +/- 3000 V can be reached through a direct connection to the system can be determined directly on the device.
Extensions
Functional extension
|
Max. DC voltage threshold
|
Display threshold exceeded
|
|
Max. AC voltage threshold
|
Display threshold exceeded
|
|
Min. DC voltage threshold
|
Displayed below threshold
|
|
times event pending
|
Time(s) for how long a threshold must be present in order to be displayed
|
|
Monitored auxiliary voltage for external sensors
|
The sensors are connected to the device and supplied via it. The power consumption is monitored and conclusions are drawn about the functionality of the sensor.
|
|
Number and time of voltage overshoot and undershoot
|
Example Only if an impulse of > 0.2 ms has occurred, this is counted and after 4 times a signal is sent
|
|
Any signal delay
|
higher-level systems only signal messages when an ACTUAL value is below or exceeded
|
|
Any signal pause / min. signal length
|
Ensuring transmission to third-party systems
|
Service
The following functions can be offered as an option. These may also require WBex components
|
Test button
|
This optional button can be used to manually activate messages or applications
|
|
Reset measured value
|
Using this option, max. or min. measured value storage can be rested 1)
|
|
Release contact
|
The release signal is required if the WB component works autonomously and should be activated or deactivated by a simple signal.
|
|
LCD display
|
ACTUAL value DC
ACTUAL value AC
Max value DC (since last reset)
Max value AC (since last reset)
|
Optional extension
Self-test function
With this extension, the two redundant measurement inputs can check themselves and detect errors.
Input signals
The functionality of the basic components can be extended by an internal extension OR by another WB component or “WBex” extension.
Output signals
The functionality of the basic components can be extended by an internal extension OR by an additional WB component.
Documents
Data sheets
No documents currently available
Data sheet
Currently no documents available
Fiches techniques
Aucun document available for the moment
Digital values
The following digital values can be passed on by the components to third-party systems or queried by third parties.
Possibilities are also listed depending on the components, configuration, installed options and system structure as well as the protocol used.
values- output
- Product type including extension
- Serial number including the extension
- Article number
- Soft and hardware versions
- ACTUAL VDC voltage at the time of request per channel
- ACTUAL VAC voltage at time of request per channel
- Date + max peak VDC value since last reset
- Date + max peak VAC value since last reset
- Date + last binary signaling e.g. threshold exceeded
- Number of switching operations per output channel since commissioning
values input
-
- threshold values / target values for switching digital outputs
- Threshold values / target values for escalation via protocol
- Software Update
- Additional parameters for configuring stored individual programs
Operational Status
- Error with error code
- Run
- Standby
- Automatic
Command
- Perform self-test
- Reset System
- Reset switch counter
- Reset measurement tips
- Switch to standby mode
- Switch to automatic mode