The functional module “WB-ADC” is used wherever electrical flows are measured and their currents are monitored. In addition, based on the collected data, the control decisions can be passed on to third-party systems.
WB-ADC
Here you can find out more VertriebsanfrageDetermines direct currents and their flow directions.
- Dielectric strength continuously 3000 VDC
- high security standard
- Description
- Function
- General data
- Technical Data
- Extensions
- Scope of delivery
- Protocols and SCADA
- Documents
- Digital Values
Function
The following measuring functions can be carried out, evaluated and displayed via digital outputs or (if available) transmitted via a protocol:
- Detects overcurrents and undercurrents
- Determines flow directions
- Energy measurement
- Storage of the maximum current value that the system has measured since the last reset or start-up
Depending on the expected current strength, the currents can be determined in different ways:
1.) Directly on the device
DC currents up to 20 A can be determined by connecting directly to the system
2.) Shunt resistance
- Integration of a shunt resistor that is connected in series in the circuit
- By external sensors up to 6kA
- Calibration sensor measurement unit
- plus auxiliary voltage +-15V/6W and a 4-20mA input
3.) Hall sensor measurement
- Integration of a Hall sensor measurement through which include the live wire.
- This eliminates the intervention in the infrastructure
- By external sensors up to 6kA
- Calibration sensor measurement unit
- plus auxiliary voltage +-15V/6W and a 4-20mA input
General data
|
Supply voltage |
24VDC /400mA |
|
Power consumption |
5-15W |
|
humidity |
0 …100%, non-condensing |
|
Outside temperature range |
-20 … 50 °C |
|
housing / design |
T2 (1 TE = 18 mm) (W x H x D) 36mm x 99mm x 105mm |
|
Modular housing |
|
|
Protection class IP 20 |
|
|
Mounted on 35 mm DIN rail according to EN 60715 |
|
|
Mains connection and inputs and outputs: |
– screw terminals, |
|
weight |
approx. 400g |
Technical Data
Analogue input channels (measuring channels)
The nominal voltages are based on the typical power supply of DC railways.
|
Input areas shunt measurement |
0-60mV |
0-1000mV |
|||
|
Hall sensor input areas |
4-20mA |
0-100mA |
0-200mA |
0-20mA |
|
|
Measurement accuracy |
see measurement channel variants |
||||
There are two variants of measurement channels
|
Product type |
withe line |
silver line |
|---|---|---|
|
Measurement channels |
2 |
|
|
Sampling Rate |
up to 15kHz |
up to 25kHz |
|
Resolution |
up to 8 bits |
up to 16 bit |
|
Measurement accuracy |
5% of max. value |
0.5% of max. value |
Output channels digital
|
number |
2 |
|
Technology |
relay with 2 separate changers (NC/ NO) |
|
switching voltage |
max. 250V |
|
switching current |
max. 8A |
|
switching capacity |
max. 2000WAC / 60W |
|
Dielectric strength coil – contact |
max. 4kVAC |
|
Switching cycles at Imax |
> 1,000,000 |
|
electrical strength contact-contact |
max. 2000VAC |
Show
Possible variants depending on the range of functions or options
|
LED1 |
green |
run |
operability permanently ON |
|
LED2 |
blue |
Enable |
Approval granted by higher authority |
|
LED3 |
green |
ON/ OFF |
Sonicated On / OFF |
|
LED4 |
red |
Error |
Functional malfunction of the system or sensors or equipment |
Operation
no controls are provided in the standard system
Extensions
Functional extension
|
Max. current threshold |
Display threshold exceeded |
|
Min. current threshold |
Displayed below threshold |
|
times event pending |
Time(s) for how long a threshold must be present in order to be displayed |
Operation
The following functions can be offered as an option. These may also require WBex components
|
Test button |
This optional button can be used to manually activate messages or applications 1) |
|
Reset measured value |
Using this option, maximum or minimum measurement values can be saved |
|
Release contact |
The release signal is required if the WB component works autonomously and is to be activated or deactivated by a simple signal |
|
LCD display |
Current current flow |
Parameterization
For security reasons and by popular demand, an on-site configuration option was omitted.
The threshold values can be set at the factory.
If you need several different threshold values in your systems, you can do this using one of our service cases Perform CM1010 / VLD1010. Different parameter sets and software updates can be stored on the service case and imported using an adapter.
It is also possible to transfer the parameters via a SCADA system (the system must be configured using connected to a WB-MC or WB-HS.
Input Signals
The functionality of the base components can be extended by an internal extension OR by another WB component or WBex extension.
|
Product |
Application examples |
|
Release contact 24VDC, |
Output signals
The functionality of the basic components can be extended by an internal extension OR by another WB component.
|
Product |
Application examples |
|
WB extensions 2 digital power outputs |
Switching an actuator or signaling contacts, e.g. 220VAC |
|
SMART OK / NOK Status |
|
|
Simple on-site extension of the component |
Scope of delivery
The following items are included in the scope of delivery:
- Instruction manual
- Installation instructions
- Unit of measurement
- Packaging
- Test report
Protocols and SCADA
|
Product |
Application examples |
|
WB – Multi-Communication |
WB component by means of which the WB component can be connected to e.g. SCADA |
|
WB – Headstation |
Any complex tasks can be implemented using these components. e.g. measurement data evaluation, graphic displays |
Documents
Datenblätter
Derzeit keine Dokumente vorhanden
Datasheet
Currently no documents available
Fiches techniques
Aucun document disponible pour le moment
Digital Values
The following digital values can be passed on from the components to third-party systems or queried by third parties.
Possibilities are also listed depending on the components, configuration, installed options and system design as well as the protocol used.
values- output
- Product type including extension
- Serial number including the extension
- Article number
- Soft and hardware versions
- IST VDC current at time of request per channel
- Date + max peak VDC current since last reset
- Date + last binary signaling e.g. threshold exceeded
- Number of switching operations per output channel since commissioning
values input
- Threshold values / target values for switching digital outputs
- Threshold values / target values for escalation via protocol
- Software update
- Additional parameters for configuring stored individual programs
operational status
- Error with error code
- Run
- Standby
- Automatic
Command
- Perform self-test
- Reset System
- Reset switch counter
- Reset measurement tips
- Switch to standby mode
- Switch to automatic mode
You may also like…
-


WBex DI4
Extension of a WB component by up to four digital inputs
Extension of a WB component by up to four digital inputs -


TVM
The analogue voltage monitoring relay TVM monitors the traction voltage of DC tracks using robust analogue measurement technology. It works without auxiliary voltage.
The analogue voltage monitoring relay TVM monitors the traction voltage of DC tracks using robust analogue measurement technology. It works… -


WBex DO2 PCBA with two digital changeover contacts.
Extension of a WB component by up to two potential-free changeover contacts
Extension of a WB component by up to two potential-free changeover contacts